Modbus

The modbus link reads and writes Modbus devices as a master (Modbus TCP, RTU over TCP, RTU on a serial port) and serves the tree’s values to Modbus masters as a slave (Modbus TCP, RTU on a serial port). It runs on the driver framework of wyrm-link-sdk, so its tree, actions, states and quality work like those of every framework driver. Decisions: ADR 0004 (the driver framework) and ADR 0024 (server kinds, the slave mode).

Code: links/modbus (wyrm-link-modbus): src/lib.rs (the driver and its params), src/codec.rs (data types, batches), src/slave.rs (slave mode), src/dsa.rs (import_dsa), src/sim.rs (the test simulator). The link is a built-in driver of wyrmd (Install Link ▸ from Driver, driver modbus) and the package modbus (wyr link pack).

1. Read this first: scaling is not DSA’s

A DSA (dslink-java-modbus) user who types the same numbers into the same labels gets wrong values without an error. Our Scaling multiplies; DSA’s divides. Use import_dsa (section 11) to move a DSA tree: it converts every point.

DSA attributeDSA meaningOur form labelOur key (json5, ~def, export)Our meaning
offsetregister or bit addressOffsetaddrregister or bit address
scalingdivisor: raw / scalingScalingscalemultiplier: raw × scale
scaling offsetadded after the divisionScaling Offsetoffsetadded after the multiplication
write of vv × scaling − scaling offset (not the inverse when scaling offset ≠ 0)(v − offset) / scale, rounded for integer types (the exact inverse)
  • Read: value = raw × scale + offset. DSA: value = raw / scaling + scaling offset.
  • In json5 and in an export, the key offset is the added offset, not the address. The address is addr.
  • Example. A DSA point has scaling = 10, scaling offset = 2, raw 250. DSA shows 27.0. The same numbers typed into our form show 250 × 10 + 2 = 2502. import_dsa sets scale = 0.1, offset = 2: the point shows 27.0, and a write of 27.0 sends raw 250.
  • Writes of imported points differ from DSA when scaling offset is not 0. A write of 27.0 sends 250 here; DSA sent 27 × 10 − 2 = 268. A device or a procedure tuned around DSA’s raw values sees other raw values after the move.
  • Float noise. scale = 1 / scaling is not exact in binary: with scaling = 10, raw 3 shows 0.30000000000000004 where DSA showed 0.3, and raw 7 shows 0.7000000000000001. Trends and equality tests in flows see this. Writes to integer types are not affected: the raw value is rounded.
  • scale = 0 is refused (scale: must not be 0); DSA scaling = 0 is not imported.

2. Tree and actions

wy/<site>/downstream/<link>/<connection>/<device>/[<folder>/…]/<point>

A connection is a socket or a serial port (or, for a slave, a listener). A device is one unit id on it. A point is a value at an address. Folders (section 10) group points below a device. Connections and devices have a status leaf (Unknown, Connecting, Connected, Failed, Stopped, Stopped by Parent), an error leaf while there is an error, and the diagnostics leaves (section 12).

NodeActionsLevel
link rootadd_ip_connection, add_serial_connection, add_ip_slave, add_serial_slave, export (the whole tree), import (a connection branch), import_dsa, rescan (Rescan For Serial Ports)config
connectionadd_device, edit, remove, copy, restart, stop / start, export, import (a device branch)config
master connectionscan_unitsconfig
deviceadd_point, add_folder, edit, remove, copy, restart, stop / start, export, import (a folder branch)config
master deviceread_registers, read_device_idread
folderadd_point, add_folder (while less than 4 deep), remove, copy, export, import (a folder branch)config
pointedit, remove, copyconfig
point value~set (writable points; every point of a slave)write

Only the action that applies is declared: stop while a node runs, start while it is stopped. DSA puts every action at READ, so anyone who can read can reconfigure; here a change of the tree needs config.

3. Parameters

Every default and bound below is the code’s (links/modbus/src/lib.rs). A param with a default may be left out. Edits are checked first: a refused edit changes nothing.

IP connection (ip_connection)

KeyLabelDefaultBoundsNotes
hostHost(required)name or IP literal; the first address it resolves to
portPort5020…65535
transportTransport Typetcptcp, rtu_over_tcprtu_over_tcp: RTU frames (CRC, no MBAP header), as serial-to-Ethernet gateways send
timeout_msTimeout (ms)1000100…10000bound on each request
write_modeWrite Modeautoauto, single, multiplesection 6
retriesRetries00…5repeats after a timeout only (section 7)

Serial connection (serial_connection)

KeyLabelDefaultBoundsNotes
serial_portSerial Port(required)a serial device path/dev/ttyS*, ttyUSB*, ttyACM*, ttyAMA*, ttySC*, ttyM*, ttyMXUSB* and other numbered Linux UART names, /dev/tty.* and /dev/cu.* (macOS), /dev/serial/by-id/*, /dev/serial/by-path/*, /dev/rfcomm*; COMn on Windows. Another path is refused (some device files have side effects on open). rescan lists the ports found.
baud_rateBaud Rate9600300…4000000
data_bitsData Bits85…8
stop_bitsStop Bits11…2
parityParitynonenone, odd, even
timeout_msTimeout (ms)1000100…10000
write_modeWrite Modeautoas above
retriesRetries00…51 is a good value on RS485

Slave connections (ip_slave, serial_slave)

KeyLabelDefaultBoundsNotes
listen_hostListen Host127.0.0.1ip_slave: every address the name resolves to (section 13)
listen_portListen Port5021…65535ip_slave; 502 needs privileges on Linux; 0 is refused (the system would pick a port no master can know)
master_idle_sMaster Idle Timeout (s)601…86400ip_slave: a master that sends no complete request for this long is closed (section 13)
serial_port, baud_rate, data_bits, stop_bits, parityas the serial connectionserial_slave

Device

KeyLabelDefaultBoundsNotes
unitSlave ID10…2550 and 255 are ordinary units on Modbus TCP; on RTU 0 is the broadcast address and is refused (section 6)
pingPingprobeprobe, fc17, noneprobe reads probe_table/probe_addr, and an exception reply means alive; fc17 sends Report Server ID (often unsupported); none sends no ping
probe_tableProbe Tableholdingcoil, discrete, input, holding
probe_addrProbe Address00…65535
ping_sPing Rate (s)5.00.1…3600
contiguous_onlyContiguous Batch Reads Onlyfalsefalse: a read may span gaps between points
max_regsMax Registers per Read1251…1251 = each register point read alone
max_bitsMax Bits per Read20001…20001 = each bit point read alone
republish_sRepublish Unchanged Values (s)00…36000 = publish on a change only; DSA republishes every 60 s

Point

KeyLabelDefaultBoundsNotes
tableObject Type(required)coil, discrete, input, holding
addrOffset(required)0…65535the value may not run past 65535
dtypeData Typeu16; binary on coil and discretesection 4a bit table holds binary only
bitBit00…15the bit of a register for binary on input/holding
regsNumber of Registers11…125registers of a char/varchar value
poll_sPoll Rate (s)1.00.01…86400
scaleScaling1.0not 0multiplier (section 1)
offsetScaling Offset0.0added after scale
writableWritablefalsecoil and holding only
unitUnit""shown beside the value
writable_by_masterWritable by Masterfalseslave connections only (coil and holding)
  • writable_by_master shows in every point form but does nothing under a master connection.
  • Under a slave connection poll_s and writable do nothing, and so do the device’s ping, probe_table, probe_addr, ping_s, contiguous_only, max_regs, max_bits and republish_s. Every point of a slave takes ~set (section 13).
  • The link root takes poll_unsubscribed (default true: points are polled all the time; false polls a group only while one of its points has a subscriber, which only process links can see: a subscription of the point or of a pattern under the link, wy/<site>/downstream/<link>/**; a wider pattern such as downstream/** does not reach the link).

4. Data types

Register words are big-endian on the wire. A multi-word value puts the most significant word first. _wswap reverses the word order, _bswap swaps the two bytes in each word, _wbswap does both (all bytes in reverse order). For the 32-bit value 0x11223344 (bytes A B C D) the registers are:

OrderRegistersOur suffix
ABCD0x1122 0x3344none
CDAB0x3344 0x1122_wswap
BADC0x2211 0x4433_bswap
DCBA0x4433 0x2211_wbswap
OursRegistersValueDSA name
binarya bit, or bit bit of 1boolBOOLEAN (any type on a coil or discrete table)
bits161array of 16 bools, bit 0 firstBOOLEAN with bit = -1 on a register
u16, i161numberUINT16, INT16
u16_bswap, i16_bswap1numberUINT16SWAP, INT16SWAP
u32, i322numberUINT32, INT32
u32_wswap, i32_wswap2numberUINT32SWAP, INT32SWAP
u32_wbswap, i32_wbswap2numberUINT32SWAPSWAP, INT32SWAPSWAP
u32_bswap, i32_bswap2numbernone
u32_m10k, i32_m10k2hi × 10000 + loUINT32M10K, INT32M10K
u32_m10k_wswap, i32_m10k_wswap2as above, words swappedUINT32M10KSWAP, INT32M10KSWAP
f322IEEE 754FLOAT32
f32_wswap2FLOAT32SWAP
f32_wbswap2none
u64, i64, f644UINT64, INT64, FLOAT64
u64_wswap, i64_wswap, f64_wswap4the four words reversedUINT64SWAP, INT64SWAP, FLOAT64SWAP
bcd1614 BCD digitsBCD16
bcd3228 BCD digitsBCD32
bcd32_wswap2words swappedBCD32SWAP
charregsASCII, trailing spaces and NULs cutCHARSTRING
varcharregsASCII up to the first NULVARCHARSTRING
  • An unscaled integer (scale 1, offset 0) publishes exactly as an unsigned or signed integer; 64-bit values never pass through a float. A scaled value publishes as a float.
  • bits16, char and varchar ignore scale, offset and bit (without an error).
  • m10k: lo must be 0…9999 for the unsigned types and −9999…9999 for the signed ones, else the point shows bad/device_error. The signed types read both words as i16, as DSA does, so halves of mixed signs are accepted.
  • An invalid BCD digit or a non-ASCII text is a point error (bad/device_error), not a value.

5. Reads

  • Points are grouped by (device, poll_s). One ticker per group; a tick is skipped while the group’s last poll is still running (no pile-up).
  • A group’s reads are planned once per table and kept until an edit: points merge into requests of at most max_regs registers or max_bits bits; gaps are read too unless contiguous_only. There is no batch switch: max_regs = 1 and max_bits = 1 read each point alone.
  • An exception reply to one request fails only the points of that request (bad/device_error, the last value kept). A timeout of every request is a device miss (section 8). When some requests of a poll time out and others answer, only the points of the timed-out requests go uncertain/stale (then bad/comm_fail), and the device stays Connected. An I/O or protocol error drops the connection; it reconnects.

6. Writes

A ~set is a request with a reply. The value is not shown before the device has it: after a write the point is read back, and after a failed write too (a series of writes may have stopped part-way), so the point shows what the device holds.

Pointautosinglemultiple
coilFC5FC5FC15
holding, 1 registerFC6FC6FC16
holding, more registersFC16a series of FC6, lowest address first (DSA “Never”)FC16
binary bit of a holding registerFC22 mask write; if the unit answers Illegal Function, read and FC6 from then on (remembered per unit while the connection lives)samesame
  • The read-modify-write of a bit always sends FC6, also in multiple mode.
  • One FC16 carries at most 123 registers. A writable char/varchar point with more regs loads and polls, but each write of it is refused (regs: a value of N registers cannot be written).
  • A value outside its type’s range, of the wrong kind or longer than its text writes nothing (invalid_parameter).
  • In single mode a failure part-way names how many registers went out.
  • Unit 0 on RTU (serial and RTU over TCP) is the broadcast address, which needs a request without a reply. tokio-modbus 0.17 always waits for a reply, so such a device sends nothing. It is accepted at add (the device does not know its connection’s kind), then shows Failed with broadcast (unit 0) is not supported on RTU; a write answers the same.
  • A set during scan_units on the same connection answers busy at once: send it again after the scan. It never waits for the scan, so it never holds the sets, actions and edits of the link’s other connections, and it is never written late. During read_registers or read_device_id (level read, one bounded request each) a set waits for that one action and then runs. The wait holds the link for up to 5 s: a read_registers to a unit that does not answer, with timeout_ms above about 4 s, outlasts it, and the set answers timeout and is not written. Keep timeout_ms low on lines where operators run read_registers while sets arrive.
  • A write that waited behind a long poll until its caller stopped waiting is dropped and answers timeout: equipment is never written late.
  • A write to a device that does not answer, with a long timeout_ms and retries, and its read-back can take longer than a client waits (10 s by default). The client then gets timeout; the point still shows what the read-back finds. A write or action that arrives during a configuration change of the same connection answers busy: send it again.

7. Timeouts, retries and RTU timing

  • Every request is bounded by timeout_ms. After a timeout it is sent again up to retries times; an exception or an I/O error is not retried. When every request of a poll times out, the poll counts as a device miss; when only some do, their points take the ladder alone (section 5).
  • After an unanswered request the transport is reopened before the next request, on every transport. On RTU a late reply would be taken for the next request of the same unit and function (tokio-modbus cannot drain input). On Modbus TCP its old transaction id would fail the next request and drop the connection. A reopened serial port first waits a guard (3.5 character times, at least 50 ms, plus the rest of the unanswered request’s window), then clears its input. Each reopen counts in the reopens diagnostic.
  • The cost of a dead unit: each of its timed-out requests costs one reopen. Behind a TCP gateway with few client slots, or on a serial port that toggles DTR on open, this can disturb the other units. Stop a dead device (stop) instead of leaving it polled.
  • Bounds on whole operations: opening the connection and a ping 4 × timeout_ms × (1 + retries); a poll timeout_ms × (1 + retries) × requests + 1 s; a write the same with its requests (one per register in a FC6 series, up to three for a bit), never less than the open bound. The 1 s covers the reopens; a poll with very many timed-out requests (about 20 or more) can still reach its bound. It is then cut and counts as a miss.
  • A failed connection reconnects after 1 s × 2^n, at most 60 s, ±20 % jitter, for ever. An edit of the connection closes it completely before the new one opens.

8. Quality

What happenedValueQuality
readthe value readgood
first poll of the device missed (timeout)last valueuncertain/stale
3 polls missedlast value; the device Failedbad/comm_fail
one batch of the device timed out while its other batches answeredlast value; the device stays Connecteduncertain/stale, after 3 such polls bad/comm_fail
the poll could not run for 3 poll periods (it waits behind a driver action, a long write series or another device’s polls that time out)last valueuncertain/stale; good again at its next read
polls miss while pings answer (a probe register that answers, a span the device drops)last value; the device Failed with the poll’s errorbad/comm_fail after 3 missed polls; it stays bad, and the device Failed, until a poll answers
exception reply for the point’s request, or a value that does not decodelast valuebad/device_error
connection downlast value; devices Stopped by Parentbad/disconnected
slave: the tree’s value does not fit the point after an editlast valuebad/config_error
the next good readthe value readgood

No miss lifts a quality: a point already bad stays bad until it is read, even when its device answers for its other points again.

There is no “zero on failed poll” (DSA writes 0, false or “” when a poll fails). A made-up value at good quality cannot be told from a real one. Here the last value stays and its quality says that it is old. A consumer checks the quality first: a flow or a display that needs a value it can act on treats uncertain/* as “may be old” and bad/* as “do not use”, and acts on its own fallback (an alarm, a safe default) if it needs one.

republish_s is a heartbeat: a value read again unchanged is published again once its last publish is that old. It follows reads, so a device that does not answer is never republished as good.

9. RS485 advice

  • Set retries = 1: one lost frame on a noisy line then does not make the points stale.
  • Give each unit a timeout_ms that fits the slowest device on the line; the whole line waits for it.
  • Stop devices that are gone (section 7).
  • serial_slave must be the only slave on its line (section 13).

10. Folders, copy, export, import

Folders

  • add_folder {name} on a device or folder. Folders nest at most 4 deep below the device. They have no params and no edit (no rename: ids are keys of history watches, ACL rules and flows; copy and remove move a branch).
  • A point id is unique on its device, in every folder. Its key gains the folder path; polls and writes do not see folders.
  • A folder may not take the name status or error, a diagnostics leaf name (section 12) or an action name.
  • remove of a folder removes everything in it, stops its polling and removes it from the stored tree.
  • A stored tree with a wrong folder structure stops the link from starting (a point id twice on a device, folders deeper than 4, an unknown key in a folder, an invalid name). This is unlike a node whose params fail: that node stays, Failed, and can be edited.

Copy

copy {name} on a connection, device, folder or point puts a deep copy beside the source.

  • A copied connection or device starts stopped: it does not poll a device twice, and a copied slave does not take its port.
  • A folder copy gives its points new ids <id>_<n> and replies with the renamed map (flows and history that name copied ids need it).
  • A copy keeps the sealed secrets (the destination is the same).

Export and import

export on a connection, device or folder replies {json}:

{"format": "wyrm-driver-branch/1", "driver": "modbus", "kind": "device",
 "name": "ahu1", "params": {…}, "enabled": true, "children": [ … ]}
  • Secrets are never exported: a secret with a value is "<not exported>".
  • import {json, name?, overwrite?}: a connection branch at the root, a device branch on a connection, a folder branch on a device or folder. name renames the top node; overwrite: true replaces a node of that name. It replies {name, reenter}: reenter lists the secrets to enter again with edit (an import never takes secrets from the text). Overwrite keeps a stored secret while the node’s destination fields stay the same.
  • A copy or import whose save fails (a full disk) changes nothing: it answers internal_error (“not saved for a restart, nothing changed”), and a node it would overwrite keeps running. Run it again once the disk works.
  • An imported connection or device starts stopped. A folder imported into a running device is polled at once (folders have no stop).
  • Bounds: 4 MiB of text, 5000 nodes, 60 s per call. The text is checked like add_* before anything changes.
  • The file format is JSON (serde_json), as the storage export of ADR 0017: a user file, not the wire codec (principle 5 keeps CBOR on the wire).

11. Import from DSA (import_dsa)

import_dsa {json, name?} at the link root takes the nodes.json of dslink-java-modbus (commit 0745d7d), or the DSA export of one connection (then name is required). Every connection is checked before the first one is imported; each imports stopped (start it after you read the report).

The report

KeyHolds
createdthe connections imported
reentersecrets to enter again (none in DSA Modbus)
dropped[{path, field, reason}]: what is not carried, or not as it was (with what was set instead)
disabled[{path, reason}]: nodes imported stopped that would only fail as they are
renamed[{from, to}]: names changed

What is converted

DSAOurs
scaling, scaling offset, offsetscale = 1 / scaling, offset = scaling offset, addr = offset (section 1)
polling interval of a device (ms)poll_s of each of its points (10 ms…24 h)
suppress non-cov update duration (ms)republish_s; missing: 60 s; 0 (publish on every poll): half the interval; at most 3600 s
Timeout (ms), retriestimeout_ms (100…10000), retries (0…5)
use multiple write commands Always / Never / As Appropriatewrite_mode multiple / single / auto
max read register count, max read bit count (connection)max_regs, max_bits (each device)
use batch polling falsemax_regs = 1, max_bits = 1
data typessection 4
foldersfolders; deeper than 4 go into the deepest
two-tier IP devices (no connection node)one connection per host and port; the first device’s connection attributes win, and the differing ones of the others are reported
  • Units are ms. polling interval, suppress non-cov update duration and Timeout are stored in ms by DSA.
  • Missing attributes get the defaults DSA restores with, not ours: Timeout 500 ms, retries 2, contiguous batch requests only true, use batch polling true; each is reported. A new connection made here has timeout_ms 1000 and retries 0.
  • Not imported, reported in dropped with the connection’s devices: UDP and ASCII transports, parity MARK and SPACE, 1.5 stop bits (section 14). No node is made, so a start cannot run them on another framing.
  • Not carried, reported in dropped: zero on failed poll set (section 8), discard data delay above 0, max write register count (one write carries up to 123 registers), values outside our bounds (clamped), local slaves (“setup local slave”: add an ip_slave by hand), nodes DSA itself does not load.
  • Imported stopped, reported in disabled: a serial connection whose port is not a serial device path on this host (COM3 on Linux or macOS): edit its serial_port, then start; a device with unit 0 on a serial connection (section 6).
  • Names: characters outside [A-Za-z0-9_.-] become _; a reserved name (status, error, a diagnostics leaf, an action name) or a taken one gets _2, _3, …; each change is in renamed.
  • A name clash refuses the whole import (a connection of that name exists): remove it, or give name for a one-connection file.
  • A failure while saving (a full disk) after some connections were imported leaves those connections imported; the error does not list them. The connection whose save failed is not imported. Look at the tree before you run the import again.

12. Diagnostics and commissioning

Diagnostics

Each connection and each device has the value leaves requests, errors, timeouts, exceptions, reopens, last_rtt_ms and avg_rtt_ms (moving average, α = 0.1). Every request sent counts, a retry too.

  • A leaf is published when it changes, at most once every 10 s, and at once when someone reads the node (its ~meta or a leaf’s).
  • A connection’s counts start at 0 when it starts or restarts, a device’s on its own start and restart. A reconnect after a failure keeps them.
  • They are ordinary values: the historian can watch them.

Commissioning actions (master connections)

ActionNodeLevelArgsReply
read_registersdevicereadtable, addr, count (1…125, default 1), dtype (optional){words} or {bits}; with dtype also value, decoded from the first registers and unscaled (or error)
read_device_iddevicereadFC43/14 basic objects, and the regular ones when the device’s conformity level has them: {vendor_name, product_code, revision, vendor_url, product_name, model_name, user_application_name} (others as object_<id>)
scan_unitsconnectionconfigfrom (default 1), to (default 247), timeout_ms (20…1000, default 200)the unit ids that answer
  • The actions run on the connection’s owner task, between polls, one request at a time. read_registers and read_device_id send each request once at the connection’s timeout_ms; the action is bounded by 12 s. A device that does not support FC43 answers not_supported.
  • One action at a time per connection. Another action of the same connection, from any caller, answers busy at once while one is queued or running; a set does during scan_units and waits during a read action (section 6). So actions delay the polls of the connection by one action at most, even when a read caller sends them without a pause.
  • scan_units sends one read of holding register 0 per unit. Any reply, an exception too, counts as an answer, except a gateway’s “target did not respond” or “path unavailable”. A transport error stops the scan (disconnected, naming the units found so far). Unit 0 is skipped on RTU. A scan whose worst case is above 165 s is refused: scan a smaller range or use a shorter timeout_ms.
  • A scan pauses the polling of its connection for its whole run: about 62 s for 247 silent units at the defaults (up to 165 s). Point values are not refreshed: after 3 poll periods they go uncertain/stale (section 8), and good again at the first poll after the scan. Sets answer busy meanwhile (section 6).
  • A scan shows in the diagnostics: a full scan of a silent range adds about one timeout and one reopen per silent unit (about 245 for the default range). That is the scan, not a failing bus.

13. Slave mode

An ip_slave (Modbus TCP) or serial_slave (RTU) connection serves its devices to masters. A device is a unit id served; a point is a view on the served coils, discrete inputs, input or holding registers of its unit (devices with the same unit, and overlapping points, share them).

Values

  • A point’s value comes from the tree: every point takes ~set (level write), input registers and discrete inputs too. What a master reads is the value after its encoding (data type, scale, offset).
  • A master may write a point with writable_by_master (coil and holding only). The written value is published as the point’s new value. The write is logged at info by point (never the value) and counted in the diagnostics; it is not in the site’s audit trail (no WYRM caller).
  • Tree sets and master requests go through one queue, so the last writer wins and the published value is what the next master read returns.
  • A point the tree never set has no value. Nothing is published for it, and a master read that touches it answers exception 4 (server device failure), never a made-up 0. The served values live in memory: a fresh link process serves nothing until the tree sets values.
  • A register of flags (binary points with different bit on one register): each bit is known when its point is set. A master read of that register answers exception 4 until every flag point on it is set; bits that no point reads are served as 0. A word view of a register needs all 16 bits.
  • A point edited to another data type gets the tree’s last value again; when that value does not fit (50000 for an i16), the point serves nothing and shows its old value as bad/config_error until it is set again.

Answers

RequestAnswer
an address no point coversexception 2 (illegal data address)
a write touching a point without writable_by_masterexception 3 (illegal data value)
a write that a point it touches cannot decode (invalid BCD, non-ASCII text, m10k low word ≥ 10000) or that makes a float NaN or infiniteexception 3; nothing changes
more registers or bits than one request carriesexception 3
a read touching a point without a valueexception 4
FC22 on a register whose points’ bits are not all knownexception 4
FC8, FC17, FC23, FC43 and every function code but FC1–6, 15, 16 and 22exception 1 (illegal function)
a unit no device servesTCP: exception 0x0B (gateway target failed to respond); RTU: no reply (another slave may have it)
the queue is full, or the answer takes more than 1 sTCP: exception 6 (busy); RTU: no reply. A request still waiting is never applied late. Under heavy load a write taken just before its 1 s ends can be applied and still answer busy; a master that sends it again writes the same value again (FC5, 6, 15, 16 and 22 give the same result twice).
RTU broadcast (unit 0) writeapplied to every served unit that takes it, no reply; counted once on the connection
RTU broadcast readignored
  • Many TCP masters send unit 255 or 0 by default. They get 0x0B unless a device has that unit: add a device with unit 255 (or 0), or set the master’s unit id. Unit 0 is refused under serial_slave (it is the broadcast).

Exposure

  • Modbus has no authentication. Anyone who reaches the port reads every served value and writes every point with writable_by_master.
  • listen_host is 127.0.0.1 by default. Another address is allowed: the link logs a warning at warn when the listener opens and shows it as attr.warning on the connection’s status leaf. Open the port only to the network of the masters (firewall, VLAN).
  • At most 16 masters are served at once by one ip_slave (on all its addresses together). A 17th master is closed as soon as it connects; it is served once another master disconnects. The request queue (64) bounds requests, this bounds sockets.
  • An idle master is closed after master_idle_s (60 s by default) without a complete request, and its place is free again: idle or half-sent connections cannot hold all 16 places. The deadline also holds while the slave waits to send a reply: a master that sends requests but never reads the replies is closed the same way. A master that polls less often than that reconnects for each poll; raise master_idle_s for it. There is no limit per source address.
  • ip_slave listens on every address the host name resolves to (localhost: ::1 and 127.0.0.1). An address the host lacks, or an address family it lacks (IPv6 turned off), is left out; no address left is an error. Any other bind error fails the connection: a port in use (after 1.5 s of retries), or no permission.
  • Port 502 needs privileges on Linux (ports below 1024): the connection shows Failed with “Permission denied”. Use a port above 1023 (for example 1502) and point the master there, or give the binary CAP_NET_BIND_SERVICE.
  • serial_slave must be the only slave on its line (point to point to one master). The tokio-modbus 0.17 RTU server reads every frame on the line as a request; other slaves’ replies on a shared RS485 bus end it, and the connection fails and reopens after backoff, losing the masters’ requests meanwhile.
  • A copy or import of a slave connection starts stopped, so two slaves never fight for a port.
  • An ip_slave binds its port when the connection starts. If the port is still held (for example by another process, or for a moment while the broker rebuilds its router), the connection goes Failed with the bind error and tries again with backoff. Nothing else is needed: wait, or pick another port (ADR 0029, decision 9).

14. Not supported, and why

WhatWhyInstead
Modbus ASCII, Modbus UDPtokio-modbus has neither; rare in the fielda gateway to TCP or RTU
parity MARK and SPACE, 1.5 stop bitsthe serial library lacks them
renameids are keys: history watches, ACL rules and flows would breakcopy, then remove
“zero on failed poll”a dishonest value at good qualitythe quality ladder (section 8)
a batch polling switchmax_regs = 1, max_bits = 1
RTU broadcast writes from a master (unit 0)tokio-modbus 0.17 always waits for a replywrite each unit
serial_slave on a shared RS485 busthe RTU server decoder (section 13)one slave per line
discard data delay, max write register count (DSA)reopen and guard after a timeout (section 7); one write carries up to 123 registers
local slave over UDP (DSA)no UDPip_slave

15. Better than DSA

What the DSA link (dslink-java-modbus, commit 0745d7d) does wrong and this link does not. These come from reading the DSA source, not from running it.

  • Rights: every DSA action is at READ, so a read-only user can add, edit and remove connections. Here a tree change needs config.
  • Reconnects: a DSA connection that fails at link start is never retried, and a serial one reconnects once only. Here a connection retries for ever with capped, jittered backoff.
  • Bit writes: DSA has no FC22 or read-modify-write: a write of a bit in a register fails with only a log line (“not a numeric array”) and writes nothing (SlaveFolder.java:551-553, 635-639, 602-605). Here: FC22, or read and FC6.
  • Inverse scaling on write: DSA writes v × scaling − scaling offset, which is not the inverse of its read when the offset is not 0. Here a write is the exact inverse of the read.
  • Writes: DSA writes fire and forget (an error goes only to the log) and the node shows the new value even when the write fails. Here a write has a reply and the point shows what the device holds.
  • Non-batch polling: in DSA one missing point ends the poll cycle for every point after it. Here each point is its own request.
  • Bad config: DSA silently deletes a node with incomplete attributes at start, and a failed add or edit only logs. Here a node that fails validation stays Failed and editable, and a refused add or edit answers invalid_parameter naming the field.
  • Edits: a DSA connection edit always stops and restores, even without a change, and does not validate. Here an edit is checked first, does nothing when nothing changed, and closes the old connection before the new one opens.
  • Storage: DSA keeps node attributes in plain nodes.json. Here the tree is sealed (ChaCha20-Poly1305) in the link’s data_dir.
  • Request order: DSA polls and pings under its master lock but sends writes outside it (whether modbus4j orders them itself was not checked). Here one owner task per connection sends every request in order.
  • Quality: DSA’s “zero on failed poll” publishes invented values; here the quality ladder tells the truth (section 8).
  • Integers: DSA passes every value through double, so a UINT64 above 2^53 loses precision. Here unscaled integers are exact.
  • DSA local slave: a write from a master after a link restart throws (the address map is not restored), an edit changes the listener only when the transport changes (not the port), a holding write takes one register as a raw short, and a UDP listener is made again for each slave on the same port. Here the slave mode serves the tree’s values in one order with the tree’s sets (section 13).

16. Test without hardware

  • wyrm-modbus-sim (cargo run -p wyrm-link-modbus --features bin --bin wyrm-modbus-sim -- --listen 127.0.0.1:5020): a Modbus TCP device with 1000 coils, discrete inputs, input and holding registers (all 0 at start), FC1–6, 15, 16, 17, 22 and 43/14. The demo’s edge site runs one for its link modbus.
  • The probe scenario modbus (links/probe/scenarios/modbus.json) runs on every site that has the link modbus with line1/ahu1 and skips the others (a modbus that is down fails it): wyr probe modbus --gateway http://127.0.0.1:8444 --site edge.
  • The driver is tested against this simulator only. It is not yet verified against diagslave or a real device.