Modbus
The modbus link reads and writes Modbus devices as a master (Modbus
TCP, RTU over TCP, RTU on a serial port) and serves the tree’s values to
Modbus masters as a slave (Modbus TCP, RTU on a serial port). It runs
on the driver framework of wyrm-link-sdk, so its tree, actions, states
and quality work like those of every framework driver. Decisions: ADR 0004
(the driver framework) and ADR 0024 (server kinds, the slave mode).
Code: links/modbus (wyrm-link-modbus): src/lib.rs (the driver and
its params), src/codec.rs (data types, batches), src/slave.rs (slave
mode), src/dsa.rs (import_dsa), src/sim.rs (the test simulator).
The link is a built-in driver of wyrmd (Install Link ▸ from Driver,
driver modbus) and the package modbus (wyr link pack).
1. Read this first: scaling is not DSA’s
A DSA (dslink-java-modbus) user who types the same numbers into the same
labels gets wrong values without an error. Our Scaling multiplies;
DSA’s divides. Use import_dsa (section 11) to move a DSA tree: it
converts every point.
| DSA attribute | DSA meaning | Our form label | Our key (json5, ~def, export) | Our meaning |
|---|---|---|---|---|
offset | register or bit address | Offset | addr | register or bit address |
scaling | divisor: raw / scaling | Scaling | scale | multiplier: raw × scale |
scaling offset | added after the division | Scaling Offset | offset | added after the multiplication |
write of v | v × scaling − scaling offset (not the inverse when scaling offset ≠ 0) | (v − offset) / scale, rounded for integer types (the exact inverse) |
- Read: value = raw ×
scale+offset. DSA: value = raw /scaling+scaling offset. - In json5 and in an export, the key
offsetis the added offset, not the address. The address isaddr. - Example. A DSA point has
scaling = 10,scaling offset = 2, raw 250. DSA shows 27.0. The same numbers typed into our form show 250 × 10 + 2 = 2502.import_dsasetsscale = 0.1,offset = 2: the point shows 27.0, and a write of 27.0 sends raw 250. - Writes of imported points differ from DSA when
scaling offsetis not 0. A write of 27.0 sends 250 here; DSA sent 27 × 10 − 2 = 268. A device or a procedure tuned around DSA’s raw values sees other raw values after the move. - Float noise.
scale = 1 / scalingis not exact in binary: withscaling = 10, raw 3 shows0.30000000000000004where DSA showed0.3, and raw 7 shows0.7000000000000001. Trends and equality tests in flows see this. Writes to integer types are not affected: the raw value is rounded. scale = 0is refused (scale: must not be 0); DSAscaling = 0is not imported.
2. Tree and actions
wy/<site>/downstream/<link>/<connection>/<device>/[<folder>/…]/<point>
A connection is a socket or a serial port (or, for a slave, a listener).
A device is one unit id on it. A point is a value at an address. Folders
(section 10) group points below a device. Connections and devices have a
status leaf (Unknown, Connecting, Connected, Failed, Stopped, Stopped by
Parent), an error leaf while there is an error, and the diagnostics
leaves (section 12).
| Node | Actions | Level |
|---|---|---|
| link root | add_ip_connection, add_serial_connection, add_ip_slave, add_serial_slave, export (the whole tree), import (a connection branch), import_dsa, rescan (Rescan For Serial Ports) | config |
| connection | add_device, edit, remove, copy, restart, stop / start, export, import (a device branch) | config |
| master connection | scan_units | config |
| device | add_point, add_folder, edit, remove, copy, restart, stop / start, export, import (a folder branch) | config |
| master device | read_registers, read_device_id | read |
| folder | add_point, add_folder (while less than 4 deep), remove, copy, export, import (a folder branch) | config |
| point | edit, remove, copy | config |
| point value | ~set (writable points; every point of a slave) | write |
Only the action that applies is declared: stop while a node runs,
start while it is stopped. DSA puts every action at READ, so anyone
who can read can reconfigure; here a change of the tree needs config.
3. Parameters
Every default and bound below is the code’s (links/modbus/src/lib.rs).
A param with a default may be left out. Edits are checked first: a refused
edit changes nothing.
IP connection (ip_connection)
| Key | Label | Default | Bounds | Notes |
|---|---|---|---|---|
host | Host | (required) | name or IP literal; the first address it resolves to | |
port | Port | 502 | 0…65535 | |
transport | Transport Type | tcp | tcp, rtu_over_tcp | rtu_over_tcp: RTU frames (CRC, no MBAP header), as serial-to-Ethernet gateways send |
timeout_ms | Timeout (ms) | 1000 | 100…10000 | bound on each request |
write_mode | Write Mode | auto | auto, single, multiple | section 6 |
retries | Retries | 0 | 0…5 | repeats after a timeout only (section 7) |
Serial connection (serial_connection)
| Key | Label | Default | Bounds | Notes |
|---|---|---|---|---|
serial_port | Serial Port | (required) | a serial device path | /dev/ttyS*, ttyUSB*, ttyACM*, ttyAMA*, ttySC*, ttyM*, ttyMXUSB* and other numbered Linux UART names, /dev/tty.* and /dev/cu.* (macOS), /dev/serial/by-id/*, /dev/serial/by-path/*, /dev/rfcomm*; COMn on Windows. Another path is refused (some device files have side effects on open). rescan lists the ports found. |
baud_rate | Baud Rate | 9600 | 300…4000000 | |
data_bits | Data Bits | 8 | 5…8 | |
stop_bits | Stop Bits | 1 | 1…2 | |
parity | Parity | none | none, odd, even | |
timeout_ms | Timeout (ms) | 1000 | 100…10000 | |
write_mode | Write Mode | auto | as above | |
retries | Retries | 0 | 0…5 | 1 is a good value on RS485 |
Slave connections (ip_slave, serial_slave)
| Key | Label | Default | Bounds | Notes |
|---|---|---|---|---|
listen_host | Listen Host | 127.0.0.1 | ip_slave: every address the name resolves to (section 13) | |
listen_port | Listen Port | 502 | 1…65535 | ip_slave; 502 needs privileges on Linux; 0 is refused (the system would pick a port no master can know) |
master_idle_s | Master Idle Timeout (s) | 60 | 1…86400 | ip_slave: a master that sends no complete request for this long is closed (section 13) |
serial_port, baud_rate, data_bits, stop_bits, parity | as the serial connection | serial_slave |
Device
| Key | Label | Default | Bounds | Notes |
|---|---|---|---|---|
unit | Slave ID | 1 | 0…255 | 0 and 255 are ordinary units on Modbus TCP; on RTU 0 is the broadcast address and is refused (section 6) |
ping | Ping | probe | probe, fc17, none | probe reads probe_table/probe_addr, and an exception reply means alive; fc17 sends Report Server ID (often unsupported); none sends no ping |
probe_table | Probe Table | holding | coil, discrete, input, holding | |
probe_addr | Probe Address | 0 | 0…65535 | |
ping_s | Ping Rate (s) | 5.0 | 0.1…3600 | |
contiguous_only | Contiguous Batch Reads Only | false | false: a read may span gaps between points | |
max_regs | Max Registers per Read | 125 | 1…125 | 1 = each register point read alone |
max_bits | Max Bits per Read | 2000 | 1…2000 | 1 = each bit point read alone |
republish_s | Republish Unchanged Values (s) | 0 | 0…3600 | 0 = publish on a change only; DSA republishes every 60 s |
Point
| Key | Label | Default | Bounds | Notes |
|---|---|---|---|---|
table | Object Type | (required) | coil, discrete, input, holding | |
addr | Offset | (required) | 0…65535 | the value may not run past 65535 |
dtype | Data Type | u16; binary on coil and discrete | section 4 | a bit table holds binary only |
bit | Bit | 0 | 0…15 | the bit of a register for binary on input/holding |
regs | Number of Registers | 1 | 1…125 | registers of a char/varchar value |
poll_s | Poll Rate (s) | 1.0 | 0.01…86400 | |
scale | Scaling | 1.0 | not 0 | multiplier (section 1) |
offset | Scaling Offset | 0.0 | added after scale | |
writable | Writable | false | coil and holding only | |
unit | Unit | "" | shown beside the value | |
writable_by_master | Writable by Master | false | slave connections only (coil and holding) |
writable_by_mastershows in every point form but does nothing under a master connection.- Under a slave connection
poll_sandwritabledo nothing, and so do the device’sping,probe_table,probe_addr,ping_s,contiguous_only,max_regs,max_bitsandrepublish_s. Every point of a slave takes~set(section 13). - The link root takes
poll_unsubscribed(default true: points are polled all the time; false polls a group only while one of its points has a subscriber, which only process links can see: a subscription of the point or of a pattern under the link,wy/<site>/downstream/<link>/**; a wider pattern such asdownstream/**does not reach the link).
4. Data types
Register words are big-endian on the wire. A multi-word value puts the
most significant word first. _wswap reverses the word order, _bswap
swaps the two bytes in each word, _wbswap does both (all bytes in
reverse order). For the 32-bit value 0x11223344 (bytes A B C D) the
registers are:
| Order | Registers | Our suffix |
|---|---|---|
| ABCD | 0x1122 0x3344 | none |
| CDAB | 0x3344 0x1122 | _wswap |
| BADC | 0x2211 0x4433 | _bswap |
| DCBA | 0x4433 0x2211 | _wbswap |
| Ours | Registers | Value | DSA name |
|---|---|---|---|
binary | a bit, or bit bit of 1 | bool | BOOLEAN (any type on a coil or discrete table) |
bits16 | 1 | array of 16 bools, bit 0 first | BOOLEAN with bit = -1 on a register |
u16, i16 | 1 | number | UINT16, INT16 |
u16_bswap, i16_bswap | 1 | number | UINT16SWAP, INT16SWAP |
u32, i32 | 2 | number | UINT32, INT32 |
u32_wswap, i32_wswap | 2 | number | UINT32SWAP, INT32SWAP |
u32_wbswap, i32_wbswap | 2 | number | UINT32SWAPSWAP, INT32SWAPSWAP |
u32_bswap, i32_bswap | 2 | number | none |
u32_m10k, i32_m10k | 2 | hi × 10000 + lo | UINT32M10K, INT32M10K |
u32_m10k_wswap, i32_m10k_wswap | 2 | as above, words swapped | UINT32M10KSWAP, INT32M10KSWAP |
f32 | 2 | IEEE 754 | FLOAT32 |
f32_wswap | 2 | FLOAT32SWAP | |
f32_wbswap | 2 | none | |
u64, i64, f64 | 4 | UINT64, INT64, FLOAT64 | |
u64_wswap, i64_wswap, f64_wswap | 4 | the four words reversed | UINT64SWAP, INT64SWAP, FLOAT64SWAP |
bcd16 | 1 | 4 BCD digits | BCD16 |
bcd32 | 2 | 8 BCD digits | BCD32 |
bcd32_wswap | 2 | words swapped | BCD32SWAP |
char | regs | ASCII, trailing spaces and NULs cut | CHARSTRING |
varchar | regs | ASCII up to the first NUL | VARCHARSTRING |
- An unscaled integer (
scale1,offset0) publishes exactly as an unsigned or signed integer; 64-bit values never pass through a float. A scaled value publishes as a float. bits16,charandvarcharignorescale,offsetandbit(without an error).m10k:lomust be 0…9999 for the unsigned types and −9999…9999 for the signed ones, else the point showsbad/device_error. The signed types read both words asi16, as DSA does, so halves of mixed signs are accepted.- An invalid BCD digit or a non-ASCII text is a point error
(
bad/device_error), not a value.
5. Reads
- Points are grouped by
(device, poll_s). One ticker per group; a tick is skipped while the group’s last poll is still running (no pile-up). - A group’s reads are planned once per table and kept until an edit:
points merge into requests of at most
max_regsregisters ormax_bitsbits; gaps are read too unlesscontiguous_only. There is no batch switch:max_regs = 1andmax_bits = 1read each point alone. - An exception reply to one request fails only the points of that request
(
bad/device_error, the last value kept). A timeout of every request is a device miss (section 8). When some requests of a poll time out and others answer, only the points of the timed-out requests gouncertain/stale(thenbad/comm_fail), and the device staysConnected. An I/O or protocol error drops the connection; it reconnects.
6. Writes
A ~set is a request with a reply. The value is not shown before the
device has it: after a write the point is read back, and after a failed
write too (a series of writes may have stopped part-way), so the point
shows what the device holds.
| Point | auto | single | multiple |
|---|---|---|---|
| coil | FC5 | FC5 | FC15 |
| holding, 1 register | FC6 | FC6 | FC16 |
| holding, more registers | FC16 | a series of FC6, lowest address first (DSA “Never”) | FC16 |
binary bit of a holding register | FC22 mask write; if the unit answers Illegal Function, read and FC6 from then on (remembered per unit while the connection lives) | same | same |
- The read-modify-write of a bit always sends FC6, also in
multiplemode. - One FC16 carries at most 123 registers. A writable
char/varcharpoint with moreregsloads and polls, but each write of it is refused (regs: a value of N registers cannot be written). - A value outside its type’s range, of the wrong kind or longer than its
text writes nothing (
invalid_parameter). - In
singlemode a failure part-way names how many registers went out. - Unit 0 on RTU (serial and RTU over TCP) is the broadcast address,
which needs a request without a reply.
tokio-modbus0.17 always waits for a reply, so such a device sends nothing. It is accepted atadd(the device does not know its connection’s kind), then showsFailedwithbroadcast (unit 0) is not supported on RTU; a write answers the same. - A set during
scan_unitson the same connection answersbusyat once: send it again after the scan. It never waits for the scan, so it never holds the sets, actions and edits of the link’s other connections, and it is never written late. Duringread_registersorread_device_id(levelread, one bounded request each) a set waits for that one action and then runs. The wait holds the link for up to 5 s: aread_registersto a unit that does not answer, withtimeout_msabove about 4 s, outlasts it, and the set answerstimeoutand is not written. Keeptimeout_mslow on lines where operators runread_registerswhile sets arrive. - A write that waited behind a long poll until its caller stopped
waiting is dropped and answers
timeout: equipment is never written late. - A write to a device that does not answer, with a long
timeout_msandretries, and its read-back can take longer than a client waits (10 s by default). The client then getstimeout; the point still shows what the read-back finds. A write or action that arrives during a configuration change of the same connection answersbusy: send it again.
7. Timeouts, retries and RTU timing
- Every request is bounded by
timeout_ms. After a timeout it is sent again up toretriestimes; an exception or an I/O error is not retried. When every request of a poll times out, the poll counts as a device miss; when only some do, their points take the ladder alone (section 5). - After an unanswered request the transport is reopened before the next
request, on every transport. On RTU a late reply would be taken for
the next request of the same unit and function (
tokio-modbuscannot drain input). On Modbus TCP its old transaction id would fail the next request and drop the connection. A reopened serial port first waits a guard (3.5 character times, at least 50 ms, plus the rest of the unanswered request’s window), then clears its input. Each reopen counts in thereopensdiagnostic. - The cost of a dead unit: each of its timed-out requests costs one
reopen. Behind a TCP gateway with few client slots, or on a serial port
that toggles DTR on open, this can disturb the other units. Stop a dead
device (
stop) instead of leaving it polled. - Bounds on whole operations: opening the connection and a ping
4 × timeout_ms × (1 + retries); a polltimeout_ms × (1 + retries) × requests + 1 s; a write the same with its requests (one per register in a FC6 series, up to three for a bit), never less than the open bound. The 1 s covers the reopens; a poll with very many timed-out requests (about 20 or more) can still reach its bound. It is then cut and counts as a miss. - A failed connection reconnects after
1 s × 2^n, at most 60 s, ±20 % jitter, for ever. An edit of the connection closes it completely before the new one opens.
8. Quality
| What happened | Value | Quality |
|---|---|---|
| read | the value read | good |
| first poll of the device missed (timeout) | last value | uncertain/stale |
| 3 polls missed | last value; the device Failed | bad/comm_fail |
| one batch of the device timed out while its other batches answered | last value; the device stays Connected | uncertain/stale, after 3 such polls bad/comm_fail |
| the poll could not run for 3 poll periods (it waits behind a driver action, a long write series or another device’s polls that time out) | last value | uncertain/stale; good again at its next read |
| polls miss while pings answer (a probe register that answers, a span the device drops) | last value; the device Failed with the poll’s error | bad/comm_fail after 3 missed polls; it stays bad, and the device Failed, until a poll answers |
| exception reply for the point’s request, or a value that does not decode | last value | bad/device_error |
| connection down | last value; devices Stopped by Parent | bad/disconnected |
| slave: the tree’s value does not fit the point after an edit | last value | bad/config_error |
| the next good read | the value read | good |
No miss lifts a quality: a point already bad stays bad until it is
read, even when its device answers for its other points again.
There is no “zero on failed poll” (DSA writes 0, false or “” when a
poll fails). A made-up value at good quality cannot be told from a real
one. Here the last value stays and its quality says that it is old. A
consumer checks the quality first: a flow or a display that needs a value
it can act on treats uncertain/* as “may be old” and bad/* as “do not
use”, and acts on its own fallback (an alarm, a safe default) if it needs
one.
republish_s is a heartbeat: a value read again unchanged is published
again once its last publish is that old. It follows reads, so a device
that does not answer is never republished as good.
9. RS485 advice
- Set
retries = 1: one lost frame on a noisy line then does not make the points stale. - Give each unit a
timeout_msthat fits the slowest device on the line; the whole line waits for it. - Stop devices that are gone (section 7).
serial_slavemust be the only slave on its line (section 13).
10. Folders, copy, export, import
Folders
add_folder {name}on a device or folder. Folders nest at most 4 deep below the device. They have no params and noedit(no rename: ids are keys of history watches, ACL rules and flows;copyandremovemove a branch).- A point id is unique on its device, in every folder. Its key gains the folder path; polls and writes do not see folders.
- A folder may not take the name
statusorerror, a diagnostics leaf name (section 12) or an action name. removeof a folder removes everything in it, stops its polling and removes it from the stored tree.- A stored tree with a wrong folder structure stops the link from
starting (a point id twice on a device, folders deeper than 4, an
unknown key in a folder, an invalid name). This is unlike a node whose
params fail: that node stays,
Failed, and can be edited.
Copy
copy {name} on a connection, device, folder or point puts a deep copy
beside the source.
- A copied connection or device starts stopped: it does not poll a device twice, and a copied slave does not take its port.
- A folder copy gives its points new ids
<id>_<n>and replies with therenamedmap (flows and history that name copied ids need it). - A copy keeps the sealed secrets (the destination is the same).
Export and import
export on a connection, device or folder replies {json}:
{"format": "wyrm-driver-branch/1", "driver": "modbus", "kind": "device",
"name": "ahu1", "params": {…}, "enabled": true, "children": [ … ]}
- Secrets are never exported: a secret with a value is
"<not exported>". import {json, name?, overwrite?}: a connection branch at the root, a device branch on a connection, a folder branch on a device or folder.namerenames the top node;overwrite: truereplaces a node of that name. It replies{name, reenter}:reenterlists the secrets to enter again withedit(an import never takes secrets from the text). Overwrite keeps a stored secret while the node’s destination fields stay the same.- A copy or import whose save fails (a full disk) changes nothing: it
answers
internal_error(“not saved for a restart, nothing changed”), and a node it would overwrite keeps running. Run it again once the disk works. - An imported connection or device starts stopped. A folder imported into a running device is polled at once (folders have no stop).
- Bounds: 4 MiB of text, 5000 nodes, 60 s per call. The text is checked
like
add_*before anything changes. - The file format is JSON (
serde_json), as the storage export of ADR 0017: a user file, not the wire codec (principle 5 keeps CBOR on the wire).
11. Import from DSA (import_dsa)
import_dsa {json, name?} at the link root takes the nodes.json of
dslink-java-modbus (commit 0745d7d), or the DSA export of one
connection (then name is required). Every connection is checked before
the first one is imported; each imports stopped (start it after you read
the report).
The report
| Key | Holds |
|---|---|
created | the connections imported |
reenter | secrets to enter again (none in DSA Modbus) |
dropped | [{path, field, reason}]: what is not carried, or not as it was (with what was set instead) |
disabled | [{path, reason}]: nodes imported stopped that would only fail as they are |
renamed | [{from, to}]: names changed |
What is converted
| DSA | Ours |
|---|---|
scaling, scaling offset, offset | scale = 1 / scaling, offset = scaling offset, addr = offset (section 1) |
polling interval of a device (ms) | poll_s of each of its points (10 ms…24 h) |
suppress non-cov update duration (ms) | republish_s; missing: 60 s; 0 (publish on every poll): half the interval; at most 3600 s |
Timeout (ms), retries | timeout_ms (100…10000), retries (0…5) |
use multiple write commands Always / Never / As Appropriate | write_mode multiple / single / auto |
max read register count, max read bit count (connection) | max_regs, max_bits (each device) |
use batch polling false | max_regs = 1, max_bits = 1 |
| data types | section 4 |
| folders | folders; deeper than 4 go into the deepest |
| two-tier IP devices (no connection node) | one connection per host and port; the first device’s connection attributes win, and the differing ones of the others are reported |
- Units are ms.
polling interval,suppress non-cov update durationandTimeoutare stored in ms by DSA. - Missing attributes get the defaults DSA restores with, not ours:
Timeout500 ms,retries2,contiguous batch requests onlytrue,use batch pollingtrue; each is reported. A new connection made here hastimeout_ms1000 andretries0. - Not imported, reported in
droppedwith the connection’s devices: UDP and ASCII transports, parity MARK and SPACE, 1.5 stop bits (section 14). No node is made, so astartcannot run them on another framing. - Not carried, reported in
dropped:zero on failed pollset (section 8),discard data delayabove 0,max write register count(one write carries up to 123 registers), values outside our bounds (clamped), local slaves (“setup local slave”: add anip_slaveby hand), nodes DSA itself does not load. - Imported stopped, reported in
disabled: a serial connection whose port is not a serial device path on this host (COM3on Linux or macOS):edititsserial_port, thenstart; a device with unit 0 on a serial connection (section 6). - Names: characters outside
[A-Za-z0-9_.-]become_; a reserved name (status,error, a diagnostics leaf, an action name) or a taken one gets_2,_3, …; each change is inrenamed. - A name clash refuses the whole import (a connection of that name
exists): remove it, or give
namefor a one-connection file. - A failure while saving (a full disk) after some connections were imported leaves those connections imported; the error does not list them. The connection whose save failed is not imported. Look at the tree before you run the import again.
12. Diagnostics and commissioning
Diagnostics
Each connection and each device has the value leaves requests, errors,
timeouts, exceptions, reopens, last_rtt_ms and avg_rtt_ms
(moving average, α = 0.1). Every request sent counts, a retry too.
- A leaf is published when it changes, at most once every 10 s, and at
once when someone reads the node (its
~metaor a leaf’s). - A connection’s counts start at 0 when it starts or restarts, a device’s
on its own
startandrestart. A reconnect after a failure keeps them. - They are ordinary values: the historian can watch them.
Commissioning actions (master connections)
| Action | Node | Level | Args | Reply |
|---|---|---|---|---|
read_registers | device | read | table, addr, count (1…125, default 1), dtype (optional) | {words} or {bits}; with dtype also value, decoded from the first registers and unscaled (or error) |
read_device_id | device | read | FC43/14 basic objects, and the regular ones when the device’s conformity level has them: {vendor_name, product_code, revision, vendor_url, product_name, model_name, user_application_name} (others as object_<id>) | |
scan_units | connection | config | from (default 1), to (default 247), timeout_ms (20…1000, default 200) | the unit ids that answer |
- The actions run on the connection’s owner task, between polls, one
request at a time.
read_registersandread_device_idsend each request once at the connection’stimeout_ms; the action is bounded by 12 s. A device that does not support FC43 answersnot_supported. - One action at a time per connection. Another action of the same
connection, from any caller, answers
busyat once while one is queued or running; a set does duringscan_unitsand waits during a read action (section 6). So actions delay the polls of the connection by one action at most, even when areadcaller sends them without a pause. scan_unitssends one read of holding register 0 per unit. Any reply, an exception too, counts as an answer, except a gateway’s “target did not respond” or “path unavailable”. A transport error stops the scan (disconnected, naming the units found so far). Unit 0 is skipped on RTU. A scan whose worst case is above 165 s is refused: scan a smaller range or use a shortertimeout_ms.- A scan pauses the polling of its connection for its whole run:
about 62 s for 247 silent units at the defaults (up to 165 s). Point
values are not refreshed: after 3 poll periods they go
uncertain/stale(section 8), andgoodagain at the first poll after the scan. Sets answerbusymeanwhile (section 6). - A scan shows in the diagnostics: a full scan of a silent range adds about one timeout and one reopen per silent unit (about 245 for the default range). That is the scan, not a failing bus.
13. Slave mode
An ip_slave (Modbus TCP) or serial_slave (RTU) connection serves its
devices to masters. A device is a unit id served; a point is a view on the
served coils, discrete inputs, input or holding registers of its unit
(devices with the same unit, and overlapping points, share them).
Values
- A point’s value comes from the tree: every point takes
~set(level write), input registers and discrete inputs too. What a master reads is the value after its encoding (data type,scale,offset). - A master may write a point with
writable_by_master(coil and holding only). The written value is published as the point’s new value. The write is logged at info by point (never the value) and counted in the diagnostics; it is not in the site’s audit trail (no WYRM caller). - Tree sets and master requests go through one queue, so the last writer wins and the published value is what the next master read returns.
- A point the tree never set has no value. Nothing is published for it, and a master read that touches it answers exception 4 (server device failure), never a made-up 0. The served values live in memory: a fresh link process serves nothing until the tree sets values.
- A register of flags (
binarypoints with differentbiton one register): each bit is known when its point is set. A master read of that register answers exception 4 until every flag point on it is set; bits that no point reads are served as 0. A word view of a register needs all 16 bits. - A point edited to another data type gets the tree’s last value again;
when that value does not fit (50000 for an
i16), the point serves nothing and shows its old value asbad/config_erroruntil it is set again.
Answers
| Request | Answer |
|---|---|
| an address no point covers | exception 2 (illegal data address) |
a write touching a point without writable_by_master | exception 3 (illegal data value) |
a write that a point it touches cannot decode (invalid BCD, non-ASCII text, m10k low word ≥ 10000) or that makes a float NaN or infinite | exception 3; nothing changes |
| more registers or bits than one request carries | exception 3 |
| a read touching a point without a value | exception 4 |
| FC22 on a register whose points’ bits are not all known | exception 4 |
| FC8, FC17, FC23, FC43 and every function code but FC1–6, 15, 16 and 22 | exception 1 (illegal function) |
| a unit no device serves | TCP: exception 0x0B (gateway target failed to respond); RTU: no reply (another slave may have it) |
| the queue is full, or the answer takes more than 1 s | TCP: exception 6 (busy); RTU: no reply. A request still waiting is never applied late. Under heavy load a write taken just before its 1 s ends can be applied and still answer busy; a master that sends it again writes the same value again (FC5, 6, 15, 16 and 22 give the same result twice). |
| RTU broadcast (unit 0) write | applied to every served unit that takes it, no reply; counted once on the connection |
| RTU broadcast read | ignored |
- Many TCP masters send unit 255 or 0 by default. They get 0x0B unless
a device has that unit: add a device with
unit255 (or 0), or set the master’s unit id. Unit 0 is refused underserial_slave(it is the broadcast).
Exposure
- Modbus has no authentication. Anyone who reaches the port reads
every served value and writes every point with
writable_by_master. listen_hostis127.0.0.1by default. Another address is allowed: the link logs a warning atwarnwhen the listener opens and shows it asattr.warningon the connection’sstatusleaf. Open the port only to the network of the masters (firewall, VLAN).- At most 16 masters are served at once by one
ip_slave(on all its addresses together). A 17th master is closed as soon as it connects; it is served once another master disconnects. The request queue (64) bounds requests, this bounds sockets. - An idle master is closed after
master_idle_s(60 s by default) without a complete request, and its place is free again: idle or half-sent connections cannot hold all 16 places. The deadline also holds while the slave waits to send a reply: a master that sends requests but never reads the replies is closed the same way. A master that polls less often than that reconnects for each poll; raisemaster_idle_sfor it. There is no limit per source address. ip_slavelistens on every address the host name resolves to (localhost:::1and127.0.0.1). An address the host lacks, or an address family it lacks (IPv6 turned off), is left out; no address left is an error. Any other bind error fails the connection: a port in use (after 1.5 s of retries), or no permission.- Port 502 needs privileges on Linux (ports below 1024): the
connection shows
Failedwith “Permission denied”. Use a port above 1023 (for example 1502) and point the master there, or give the binaryCAP_NET_BIND_SERVICE. serial_slavemust be the only slave on its line (point to point to one master). Thetokio-modbus0.17 RTU server reads every frame on the line as a request; other slaves’ replies on a shared RS485 bus end it, and the connection fails and reopens after backoff, losing the masters’ requests meanwhile.- A copy or import of a slave connection starts stopped, so two slaves never fight for a port.
- An
ip_slavebinds its port when the connection starts. If the port is still held (for example by another process, or for a moment while the broker rebuilds its router), the connection goesFailedwith the bind error and tries again with backoff. Nothing else is needed: wait, or pick another port (ADR 0029, decision 9).
14. Not supported, and why
| What | Why | Instead |
|---|---|---|
| Modbus ASCII, Modbus UDP | tokio-modbus has neither; rare in the field | a gateway to TCP or RTU |
| parity MARK and SPACE, 1.5 stop bits | the serial library lacks them | |
rename | ids are keys: history watches, ACL rules and flows would break | copy, then remove |
| “zero on failed poll” | a dishonest value at good quality | the quality ladder (section 8) |
| a batch polling switch | max_regs = 1, max_bits = 1 | |
| RTU broadcast writes from a master (unit 0) | tokio-modbus 0.17 always waits for a reply | write each unit |
serial_slave on a shared RS485 bus | the RTU server decoder (section 13) | one slave per line |
discard data delay, max write register count (DSA) | reopen and guard after a timeout (section 7); one write carries up to 123 registers | |
| local slave over UDP (DSA) | no UDP | ip_slave |
15. Better than DSA
What the DSA link (dslink-java-modbus, commit 0745d7d) does wrong and
this link does not. These come from reading the DSA source, not from
running it.
- Rights: every DSA action is at
READ, so a read-only user can add, edit and remove connections. Here a tree change needsconfig. - Reconnects: a DSA connection that fails at link start is never retried, and a serial one reconnects once only. Here a connection retries for ever with capped, jittered backoff.
- Bit writes: DSA has no FC22 or read-modify-write: a write of a bit
in a register fails with only a log line (“not a numeric array”) and
writes nothing (
SlaveFolder.java:551-553, 635-639, 602-605). Here: FC22, or read and FC6. - Inverse scaling on write: DSA writes
v × scaling − scaling offset, which is not the inverse of its read when the offset is not 0. Here a write is the exact inverse of the read. - Writes: DSA writes fire and forget (an error goes only to the log) and the node shows the new value even when the write fails. Here a write has a reply and the point shows what the device holds.
- Non-batch polling: in DSA one missing point ends the poll cycle for every point after it. Here each point is its own request.
- Bad config: DSA silently deletes a node with incomplete attributes
at start, and a failed add or edit only logs. Here a node that fails
validation stays
Failedand editable, and a refused add or edit answersinvalid_parameternaming the field. - Edits: a DSA connection edit always stops and restores, even without a change, and does not validate. Here an edit is checked first, does nothing when nothing changed, and closes the old connection before the new one opens.
- Storage: DSA keeps node attributes in plain
nodes.json. Here the tree is sealed (ChaCha20-Poly1305) in the link’sdata_dir. - Request order: DSA polls and pings under its master lock but sends writes outside it (whether modbus4j orders them itself was not checked). Here one owner task per connection sends every request in order.
- Quality: DSA’s “zero on failed poll” publishes invented values; here the quality ladder tells the truth (section 8).
- Integers: DSA passes every value through
double, so aUINT64above 2^53 loses precision. Here unscaled integers are exact. - DSA local slave: a write from a master after a link restart throws
(the address map is not restored), an edit changes the listener only
when the transport changes (not the port), a holding write takes one
register as a raw
short, and a UDP listener is made again for each slave on the same port. Here the slave mode serves the tree’s values in one order with the tree’s sets (section 13).
16. Test without hardware
wyrm-modbus-sim(cargo run -p wyrm-link-modbus --features bin --bin wyrm-modbus-sim -- --listen 127.0.0.1:5020): a Modbus TCP device with 1000 coils, discrete inputs, input and holding registers (all 0 at start), FC1–6, 15, 16, 17, 22 and 43/14. The demo’s edge site runs one for its linkmodbus.- The probe scenario
modbus(links/probe/scenarios/modbus.json) runs on every site that has the linkmodbuswithline1/ahu1and skips the others (amodbusthat is down fails it):wyr probe modbus --gateway http://127.0.0.1:8444 --site edge. - The driver is tested against this simulator only. It is not yet
verified against